NextGenergy — Make every watt countTalk to our team
Tools · 03

Ten boundaries. Three questions. Thirty points.

Tick only what you could hand to an auditor today, not what you believe was done. The score stays in your browser. Nothing is sent to us.

Your score
0 / 30

Start ticking.

Checklist version: 2026-09. Boundaries marked N/A are removed from the maximum.

The same ten boundaries as the reference list. Column headings: Was it tested? · Against written acceptance criteria? · Is the record retrievable now?

Swipe sideways to see all columns.

#BoundaryWas it tested?Against written acceptance criteria?Is the record retrievable now?N/A
01Cold plate joints
At the server
02Quick disconnects
At the server
03Hose crimps
At the server
04Manifold branches
In the rack
05Elastomeric seals
In the rack
06Threaded, compression and adapter fittings
In the rack
07Internal boundaries
In the CDU
08Field welds and hot work
Between the CDU and the facility
09Balancing and isolation valves
Between the CDU and the facility
10Fill, drain, vent and sample ports
Between the CDU and the facility

Questions this page answers

Where does my score go?

Nowhere outside your browser. Your ticks are saved in this browser's local storage so they survive a reload; nothing is sent to NextGenergy or anyone else. Use Reset to clear them. They do not sync across devices. Export CSV saves a file to your own computer only.

What counts as a record?

Something you could hand to an auditor today: a test sheet with a date, a technician and a result, a factory certificate indexed to a serial number, a connection log entry. A verbal assurance or a line in a schedule saying the test was planned does not count. The turnover package, boundary by boundary →