Selected with the server OEM, verified by factory pressure test traceable to serial.
Cold plates are usually specified by the server OEM and we rarely get to choose them. What we can do is require the evidence: a factory pressure or helium test traceable to the plate's serial, and a thermal performance figure stated at a flow and inlet temperature that match the loop we are designing, not the datasheet's best case.
Thermal performance at the plate depends on everything upstream. A plate rated at 1.5 L/min and 30 °C inlet will not deliver the same case temperature at 40 °C inlet in a loop that has fouled. We design the loop to the plate's real operating point and record that point at commissioning.